Huawei OLT EA5800-X7
$3,500.00 $2,600.00
Brand: Huawei
Model: EA5800-X7
Detail: Huawei OLT EA5800 Series EA5800-X2/X7/X15/X17
Condition: 100% New
Availability: IN STOCK
- Description
- Features
- Ordering information
- Inquiry
Appearance and Structure

Similar products:EA5800-X17 EA5800-X15 EA5800-X2

ESD Jack
The ESD jack of the EA5800-X7 service subrack is on the bottom of the fan tray and is used to connect the ESD wrist strap to prevent device damage caused by electrostatic discharge.
Grounding

Connect the ground cables properly to guarantee protection against lightening and interference for the EA5800-X7 subrack. When a Huawei cabinet is installed, the service subrack is grounded through mounting ears and therefore no separate ground cables are required. When a third-party cabinet is installed, a separate ground cable is needed to connect the service subrack to the ground point on the cabinet.
The EA5800-X7 subrack has 2 ground points. One is on the left side panel and the other is in the middle of the right mounting bracket of the subrack.
The power input end of the EA5800-X7 has a noise filter. The center ground of the noise filter connects to the subrack, known as the chassis ground or protection ground. Ground the subrack enclosure securely to divert the induced or leaked current to the ground and improve the protection against electromagnetic interference.
Use a ground cable to connect the ground point of the subrack enclosure to the ground bar of the telecommunications room or to the ground directly. It is recommended that the grounding resistance of the telecommunications room should be less than 10 ohms. Refer to the local standards before grounding the subrack.
Physical Specifications
Dimensions and Weight
Specification | Value |
---|---|
Dimensions (H x W x D, excluding mounting ears) | 263.9 mm x 442.0 mm x 268.7 mm |
Dimensions (H x W x D, including mounting ears of IEC standard) | 263.9 mm x 482.6 mm x 268.7 mm |
Dimensions (H x W x D, including mounting ears of ETSI standard) | 263.9 mm x 535.0 mm x 268.7 mm |
Weight (fully configured, including mounting ears) | 26 kg |
Power Supply
Power Consumption
Typical Configuration | Static Power Consumption | Maximum Power Consumption | Typical Power Consumption | Board Configuration |
---|
Typical Configuration | Static Power Consumption | Maximum Power Consumption | Typical Power Consumption | Board Configuration |
---|---|---|---|---|
GPON | 296 | 721 | 508.5 | H902MPLAE*2+H901PILA*2+H901FMMA+H901GPSFE*7 |

The power consumption of a service subrack is calculated based on the following conditions:
- Operating voltage: -53.5 V DC.
- Ambient temperature: 25°C.
- Static power consumption: All ports are idle, and no optical module is inserted to any optical port.
- Maximum power consumption: All ports are running at full capacity.
- Typical power consumption: half of the total value of the static power consumption and maximum power consumption.
- To calculate the actual power consumption, use the Access Network Hardware Configuration Tool.
- The power consumption of access devices is generally transformed into heat consumption. Therefore, heat consumption (BTU/h) and power consumption (W) can be converted to each other using this formula: 1 BTU/h = 0.2931 W.
Slot Configuration
H901BPMB is the backplane supported by the EA5800-X7.
Table 1 lists the configuration of boards in the EA5800-X7.
Slot Type | Slot | Supported Board | Remarks |
---|
Slot Type | Slot | Supported Board | Remarks |
---|---|---|---|
Control board slot | 8,9 | Control board | The active and standby control boards must be configured, and the 2 boards must be of the same type. |
Power board slot | 10,11 | Power board | - |
Universal interface board slot | 0 | Universal interface board | - |
Service board slot | 1-7 |
|
|
Fan Tray
The fan tray of the EA5800-X7 service subrack has 6 fans and a fan monitoring board FMMA and supports heat dissipation, monitoring, and fan speed adjustment to ensure that the device works at a proper temperature.

Specification
Item | Specification |
---|---|
Dimensions (H x W x D) | 43.6 mm x 257.5 mm x 260.4 mm |
Weight | 2.00 kg (Fan tray) |
Power consumption |
|

The power consumption of access devices is generally transformed into heat consumption. Therefore, heat consumption (BTU/h) and power consumption (W) can be converted to each other using this formula: 1 BTU/h = 0.2931 W.
Function
The functions of the fan tray are as follows:
- Heat dissipationThe fan tray is on the right side of the service subrack to exhaust hot air. The air flow is from left to right.
- MonitoringThe fan monitoring board detects whether the fans are working in a normal state and sends the results to the control board periodically.
- Speed adjustmentThe rotating speed of the fans can be adjusted manually or automatically based on the detected temperature.
Indicator
Indicator | Color | Status | Meaning | Operation Description |
---|
Indicator | Color | Status | Meaning | Operation Description |
---|---|---|---|---|
STATUS | Yellow | Blinking quickly (on for 0.125 s and off for 0.125 s repeatedly) | The fan tray is not registered, is being loaded, or fails to communicate with the control board. |
|
Green | Blinking | The fan tray works in the normal state. | No action is required. | |
Yellow | Blinking slowly (on for 1 s and off for 1 s repeatedly) | The fan tray generates alarms that do not affect services. | Handle it based on the corresponding alarm. | |
Red | Blinking | The fan tray is faulty or the fan tray generates an over-temperature alarm. |
|
Fan Speed Adjustment
The fan speed adjustment mode can be set to "automatic" or "manual" in the command line interface (CLI). The default mode is "automatic".

The fan tray is used for heat dissipation of the system so that the device can work at a normal temperature. When the ambient temperature exceeds the upper limit, the system automatically reports a high temperature alarm.
- Automatic mode
- Based on the control system: The control system automatically adjusts the fan speed according to the board temperatures for energy conservation.
- Based on the monitoring board: The control system adjusts the fan speed based on the temperature information collected by the monitoring board.
NOTE:
When the automatic speed adjustment mode is used, the device automatically switches between adjustment based on the control system and the adjustment based on the monitoring board.
- Manual modeYou can also manually adjust the fan speed to a level between level 0 (the lowest speed) and level 6 (the highest speed) or a percentage between 20% and 100% using commands.
Heat Dissipation
Model: EA5800-X7
Detail: Huawei OLT EA5800 Series EA5800-X2/X7/X15/X17
Availability: IN STOCK